CASE STUDY: dairy industry scrubber upgrade
UPGRADING A SCRUBBER IN THE DAIRY INDUSTRY
A scrubber that had been in service for 7 years at a dairy industry site was no longer delivering the required performance. The cause was not the age of the system, but components unsuited to its operating conditions. In the meantime, a regulatory update required the operating hours to be recorded. BMB worked on the existing scrubber, upgrading its instrumentation and control logic.

CLIENT’S NEED
Bring an existing scrubber back to the required performance and bring it into line with the new regulations, which require the system’s operating hours to be recorded.

TECHNOLOGY EMPLOYED
Updated control logic
Hour meter
Automatic reagent dosing system
Differential pressure switch with alarm threshold

RESULTS
Operating hours recorded, as required by the regulations
More precise reagent dosing than the previous system
Automatic alarm when the scrubber packing needs cleaning

STRENGTHS
Work carried out on the existing system
Less reagent waste
Cleaning scheduled on the basis of a measured value
that others don’t know how to treat.
AMONG OUR CLIENTS
DAIRY INDUSTRY SCRUBBER UPGRADE: THE CONTEXT
The scrubber treats the air from a wastewater treatment plant serving a dairy factory. The client already knew BMB’s work, as BMB had looked after other plants in the same group, and, satisfied with the results, asked BMB to work on this one too.
Although it had been in service for only 7 years, the system had been fitted with components unsuited to its operating conditions, and its performance had declined. In the meantime, a regulatory update required the actual operating hours to be recorded, to show that the scrubber was really running.

THE BMB PURIFICATION SOLUTION

CHALLENGES
A RECENT SYSTEM TO BRING BACK TO THE REQUIRED PERFORMANCE
- Restoring the scrubber’s performance without replacing it.
- Bringing the system into line with the new regulations on recording operating hours.
- Correcting reagent dosing that sometimes fell short and sometimes overshot, at unnecessary cost.
- Knowing when to clean the packing, without waiting for performance to drop.
SOLUTION
FOUR UPGRADES TO THE EXISTING SCRUBBER
Updated control logic. The logic that runs the scrubber was modernised to integrate the new components.
Hour meter. It records the system’s actual operating hours. The operator can therefore check, and show to inspectors, whether and for how long the scrubber has been running.
Automatic reagent dosing. At times the previous system did not dose at all, and at others dosed too much, even when it was not needed: more reagents were used, and so more money was spent than necessary. The new automatic system is more precise and effective, so reagents are used more efficiently.
Differential pressure switch with alarm threshold. It measures the pressure drop of the air across the scrubber packing. As the packing gets dirty, the pressure drop rises: when it exceeds the set threshold, an alarm is triggered to signal that the packing needs cleaning.


MANUFACTURING AND INSTALLATION
Each plant produced by BMB is designed, built and tested in-house. The installation is planned and carried out by our specialised technicians.

MAINTENANCE ASSISTANCE
BMB offers a complete, customised assistance and maintenance service for its plants: routine maintenance, call-out availability for extraordinary work and remote monitoring.

PLANT DESIGN
Our plants are designed in compliance with the latest legal and engineering standards and tailored to each client’s needs to optimise the investment.
FAQs: questions and answers
When is it better to upgrade a scrubber rather than replace it?
When the structure is in good condition and the problems come from components, instrumentation or control logic. In these cases, targeted work can bring the system back to the required performance without rebuilding it from scratch.
What is a differential pressure switch used for in a scrubber?
It measures the pressure difference upstream and downstream of the packing. If the difference rises above a threshold, the packing is dirty or clogged and needs cleaning.
Why fit an hour meter to an abatement system?
To record its actual operating hours. Emission permits may require this figure, and it shows that the system was running whenever production was.